16 Monitor ISM/xL™ Hardware Guide
22-0375 rev1.1
SENSOR
CATEGORY
DESCRIPTION DEFAULT
SETTINGS
Cnt Door Window Contact (surface mount)
- also used as an RF transmitter for hard wire inputs
- e.g. Overhead Door Contacts
3.
.
FrP Fire Pull 3. .
Frz Freeze Temperature Detector 3..
Gls Glass Break Detector 3..
HKP Hand Held Keypad 0. .
PIR Passive Infra-red Detector 3..
Pnc Panic Pendant OR Hand Held Double Button Panic 0. .
Rcn Recessed Contact 3..
RoR Rate of Rise Detector 3. .
Smk Smoke Detector 3. .
SoS Shock and Sound Detector 3..
??? Unknown sensor type – delete this sensor and re-learn
Testing (Signal Strength)
• Use the Service PIN to go to the TEST menu.
• Select App for application module and then W/L for wireless.
• Select Scan. Activate a sensor.
• The screen will display information about each sensor it receives. E.g. Cnt56DB5 (door/window contact and its
address),
014 (input #14), 80 02 4 (sensor transmit codes).
• Press XESC escape to return to the TEST screen. Press Signal.
• Activate a sensor. Screen indicates signal strength of sensor it receives. E.g. “Strength is 8 !”. Signal strength of
7 to 8 is acceptable. Signal strength of 6 or less is poor to unacceptable. The input point # transmitting will also
indicate:
(Tx: 014).
• Another method to check if a sensor is transmitting is to stand near the RF module holding a sensor and activate
the sensor. The large green LED, visible through the module’s cover will flash upon activating the sensor to
indicate signal transmission.
• RF Module sensor inputs OK or Not OK and Tamper can be checked in System Status/Area/Points.
• RF Module, hand held keypad(s) and sensor status can be checked in System Status under App – Wireless
using the left or right arrow LCD keypad keys for conditions such as low battery, sensor loss. Disregard any codes
in lower right corner of these screens.